DIN EN 12285-1/A100:2017-02
Workshop fabricated steel tanks - Part 1: Horizontal cylindrical single skin and double skin tanks for the underground storage of flammable and nonflammable water polluting liquids other than for heating and cooling of buildings; Amendment A100
Summary
The Standard specifies the requirements for shop fabricated cylindrical, horizontal tanks, single and double skin for underground storage of water polluting liquids (both flammable and non-flammable) within the following limits: - from 800 mm up to 3000 mm nominal diameter; - up to a maximum overall length of 6 times the nominal diameter; - for liquids with a maximum density of up to 1,9 kg/l; - with an operating pressure (po) of maximum 1,5 bar (abs.) and - for double skin tanks with a vacuum leak detection system where the kinematic viscosity does not exceed 5 x 10-3 m2/s. This standard is applicable for normal operating temperature conditions (-20 °C to +50 °C).
Notes
Prévu comme amendement à DIN EN 12285-1 (2003-07).
Technical characteristics
| Publisher | Deutsche Institut für Normung e.V. (DIN) |
| Publication Date | 02/01/2017 |
| Cancellation Date | 12/01/2018 |
| Page Count | 3 |
| EAN | --- |
| ISBN | --- |
| Weight (in grams) | --- |